Main
range of product
PowerPact multistandard

range
PowerPact

product name
H-Frame

device short name
H-Frame

product or component type
Circuit breaker

device application
Distribution

Complementary
poles description
3P

control type
Toggle

mounting mode
Unit mount

mounting support
Backplate
DIN rail
Flush

electrical connection
Terminal nut line side
Terminal nut load side

[In] rated current
100 A at 40 °C

[Ui] rated insulation voltage
750 V AC at 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2

[Ue] rated operational voltage
525 V AC at 50/60 Hz conforming to IEC 60947-2
690 V AC at 50/60 Hz conforming to IEC 947-2
600 V AC at 50/60 Hz conforming to UL 489

breaking capacity code
HG

suitability for isolation
Yes

utilisation category
Category A

mechanical durability
4000 cycles

electrical durability
4000 cycles

connection pitch
45 mm

local signalling
ON/OFF indication

contact position indicator
Yes

trip unit name
TM

trip unit technology
Thermal-magnetic

trip unit protection functions
Basic protection

trip unit rating
100 A

display type
3 LEDs

breaking capacity
65 kA at 240 V - AC conforming to UL 489
35 kA at 480 V - AC conforming to UL 489
18 kA at 600 V - AC conforming to UL 489
Icu : 65 kA at 220/240 V - AC conforming to IEC 947-2
Icu : 35 kA at 380/415 V - AC conforming to IEC 947-2
Icu : 35 kA at 440/480 V - AC conforming to IEC 947-2
Icu : 18 kA at 500/525 V - AC conforming to IEC 947-2

[Ics] rated service breaking capacity
Ics : 65 kA at 220/240 V - AC conforming to IEC 947-2
Ics : 35 kA at 380/415 V - AC conforming to IEC 947-2
Ics : 35 kA at 440/480 V - AC conforming to IEC 947-2
Ics : 18 kA at 500/525 V - AC conforming to IEC 947-2

long time pick-up adjustment type Ir
Fixed

long time pick-up adjustment range
1 In

short-time pick-up adjustment type Isd
Fixed

[Isd] short-time pick-up adjustment range
1700 A

overvoltage category
II

provision for padlocking
Non padlockable

height
163 mm

width
104 mm

depth
86 mm

standards
IEC 60947-2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
W-C-375B/GEN

product certifications
CCC
CE

product weight
2.2 kg

Environment
IP degree of protection
IP40 conforming to IEC 60529

IK degree of protection
IK07 conforming to IEC 62262

pollution degree
3 conforming to IEC 60664-1
3 conforming to IEC 60947-1

ambient air temperature for operation
40 °C

ambient air temperature for storage
-50...85 °C