Operating voltage DC |
|
UB
|
21 ... 24 ... 27 V DC Regulated, residual ripple < 5 % |
Current consumption |
|
(with relay energized) |
150 mA
|
Fusing |
|
External (operating voltage UB) |
0,25 ... 8 A |
EMC protection requirements |
In acc. with EN 60947-5-3 |
Degree of contamination (external, according to EN 60947-1) |
2 |
Connection cross-section |
|
(screw terminals) |
0,25 ... 2,5 mm² |
Current via feedback loop |
5 ... 8 ... 10 mA |
permissible resistance in feedback loop |
max.600 Ω |
|
Safety contacts 13/14, 23/24 |
Type of output |
Relay contacts, floating |
Switching current |
|
At switching voltage AC/DC 17 ... 30 V |
15 ... 6000 mA |
At switching voltage AC/DC 1 ... 60 V |
1 ... 300 mA
|
At switching voltage AC 17 ... 230 V |
15 ... 1500 mA |
Fusing |
|
External (safety circuit) according to EN 60269-1 |
6 AgG or 6 A circuit breaker (characteristic B or C) |
Utilization category acc. to EN 60947-5-1 |
|
AC-15 |
230 V 1.5 A |
DC-13 |
24 V 1.2 A |
AC-12 |
30 V 6 A |
|
60 V 0.3 A |
DC-12 |
60 V 0.3 A |
|
30 V 6 A |
Switching load |
|
According to c UL us |
Class 2 max. 30 V AC / Class 2 max. 60 V DC; 120 V AC 3 A / 240 V AC 1.5 A |
Rated insulation voltage Ui
|
250 V |
Rated impulse withstand voltage Uimp
|
4 kV |
Rated conditional short-circuit current |
100 A |
Discrepancy time |
|
(Between the operating points of both relays, with 4 active actuators) |
max.400 ms |
|
STATE LED |
LED indicator |
Status LED |
|
LED OUT |
LED indicator |
Safety outputs status |
|
DIA LED |
LED indicator |
Diagnostics LED |
|
Monitoring outputs: Diagnostic DIA, door monitoring outputs O1,O2,O3,O4 |
Type of output |
Semiconductor output, p-switching, short circuit-proof |
Output voltage |
0,8 x UB ... UB V DC |
Output current |
max.20 mA |
|
Inputs: Start button S, test input TST |
Input current |
|
HIGH |
5 ... 8 ... 10 mA |
Input voltage |
|
LOW |
0 ... 2 V DC |
HIGH |
15 ... UB V DC |